Quotation of Electrical Continuously Transposed Conductor to Malaysla use for Transformer

    1.CONTINUOUSLY TRANSPOSED CONDUCTOR (CTC), 90-309 QTY:50610

    NOTES FOR CTC:-
    1) SUPPLIER TO FORWARD INSTRUCTION MANUAL: DRYING AND CURING OF EPOXY COATED CONDUCTOR FOR SINGLE WINDING.
    2) SUPPLIER TO FORWARD CTC TECHNICAL SPECIFICATION FOR MTM REFERENCE.
    3) SUPPLIER TO FORWARD TECHNICAL DATA SHEET (TDS) FOR MTM APPROVAL BEFORE PRODUCTION.
    4) Inner layer: (Insulation paper manufacturer from Weidmann, (Switzerland/ China) or Munskjo, Sweden or Pucaro, Germany) only.
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1.
    Inner layer shall be butt lap without gap and each layer staggering with respect to the underlying layer by 30%.
    No. of paper layer = 2 (min)
    5) Outermost layer: (Insulation paper manufacturer from Weidmann, (Switzerland/ China) or Munskjo, Sweden or Pucaro, Germany) only.
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1.
    Outermost 2 layers shall be interlock by 50%.
    6) Electrical resistivity should be less than 0.01724 Ω mm2/m @ 20 oC.
    7) Supplier to forward test certificate for insulation paper, copper conductor, enamel and epoxy coated before manufacturing for MTM approval.
    8) No. of transposition shall be provided in supplier Data Sheet.
    9) Dimensional detail of CTC (after epoxy coated CTC cured and compressed condition) shall be submitted to MTM for review and approval.
    10) Paper covering shall be closely packed without gaps. CTC shall be free from twist & other form of distortion. Paper covering shall be tight and free from
    crack, puncture and inclusion of foreign matters, creases and other defects. Loose covering is NOT ACCEPTABLE.
    11) Drum size: Flange (max) 1600 mm, Outer width (max) 1000 mm, Bore (min) 120 mm, weight per drum + copper (max) 5000 kg

    Requirement per Job= 7,230kg
    Total job required:
    PMU Kedah Rubber = 2 Job
    PMU Store Bukit Sentosa = 2 Job
    PMU Vallombrosa = 2 Job
    PMU Store Bukit Sentosa = 1 Job

    2.BUNCH CONDUCTOR – RADIAL TRIPPLE,90-309, QTY:79968

    NOTE FOR BUNCH CONDUCTOR:- 10157 dd
    1) SUPPLIER TO FORWARD BUNCHED TECHNICAL SPECIFICATION FOR MTM REFERENCE.
    2) SUPPLIER TO FORWARD TECHNICAL DATA SHEET (TDS) FOR MTM APPROVAL BEFORE PRODUCTION.
    3) Inner layer:
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1. Inner layer shall be applied in butt lap without gap in the butt.
    Each layer shall be staggered with respect to the underneath layer by 33% of paper width (approx.).
    4) Outermost layer: (Insulation paper manufacturer from 1) Weidmann, (Switzerland/ China). 2) Munskjo, Sweden. 3) Pucaro, Germany)
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1. Outermost 2 layers shall be interlock by 50%.
    5) Supplier to confirm width of paper before manufacturing.
    6) Supplier to forward test certificate for insulation paper and copper conductor before manufacturing for MTM approval.
    7) Drum size: Flange (max) 1016 mm, Outer width (max) 300 mm, Bore (min) 70 mm, weight per drum + copper (max) 500 kg

    Requirement per Job= 11,424 kg
    Total job required:
    PMU Kedah Rubber = 2 Job
    PMU Store Bukit Sentosa = 2 Job
    PMU Vallombrosa = 2 Job
    PMU Store Bukit Sentosa = 1 Job

    3.PAPER INSULATED RECTANGULAR COPPER CONDUCTOR (PICC),90-309, 90-309 QTY:11361

    Requirement per Job= 1,623 kg
    Total job required:
    PMU Kedah Rubber = 2 Job
    PMU Store Bukit Sentosa = 2 Job
    PMU Vallombrosa = 2 Job
    PMU Store Bukit Sentosa = 1 Job

    4.HV Contra Shield, 90-309 QTY:427

    NOTES FOR PICC:-
    1) Rp 0.2 % proof stress (Mpa) : Min. 200 for Regulating copper & Min. 190 for HV contra shield copper
    2) SUPPLIER TO FORWARD TECHNICAL DATA SHEET (TDS) FOR MTM APPROVAL BEFORE PRODUCTION.
    3) Type of papers and test requirements:
    As per MS-16, Specification For Paper Covered Rectangular Copper Conductor, Rev.2)
    4) Inner layer: (Insulation paper manufacturer from 1) Weidmann, (Switzerland/ China). 2) Munskjo, Sweden. 3) Pucaro, Germany)
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1. Inner layer shall be applied in butt lap without gap in the butt.
    Each layer shall be staggered with respect to the underneath layer by 33% of paper width (approx.).
    5) Outermost layer: (Insulation paper manufacturer from 1) Weidmann, (Switzerland/ China). 2) Munskjo, Sweden. 3) Pucaro, Germany)
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1. Outermost 2 layers shall be interlock by 50%.
    6) Supplier to confirm width of paper before manufacturing.
    7) Supplier to forward test certificate for insulation paper and copper conductor before manufacturing for MTM approval.
    8) Drum size: Flange (max) 1016 mm, Outer width (max) 300 mm, Bore (min) 70 mm, weight per drum + copper (max) 500 kg

    Requirement per Job= 61 kg
    Total job required:
    PMU Kedah Rubber = 2 Job
    PMU Store Bukit Sentosa = 2 Job
    PMU Vallombrosa = 2 Job
    PMU Store Bukit Sentosa = 1 Job

    5.CONTINUOUSLY TRANSPOSED CONDUCTOR (CTC), 45-305, QTY:1874

    Requirement per Job= 937 kg
    Total job required:
    PMU Pasir Besar = 2 Job

    6.LV Winding, QTY:8376

    NOTE FOR CTC:- 4032
    1) Type of papers and test requirements:
    1.1) As per MS-43, Specification for Continuously Transposed Conductor (CTC), Rev. 1
    1.2) Paper covering shall be applied on CTC by helical lapping of paper tapes with all layers in same direction. Paper lapping shall be tight and
    continuous in each layer. No adhesive or bonding material shall be used except for anchoring paper end.
    2) Inner layer: (Insulation paper from Weidmann, Munskjo and Pucaro only)
    2.1) Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1.
    2.2) Inner layers (Kraft paper) shall be applied in butt-laps without any gap in the butt. Each layer shall be staggered (progressively displaced) with
    respect to the underneath layer, by 33% of paper width.
    3) Outermost layer: (Insulation paper from Weidmann, Munskjo and Pucaro only)
    3.1) Thermally Upgraded Insulated paper as per IEC 60554-3-5, grade 5A4-1M1
    3.2) Outermost two layers shall be interlocked by 50% paper width
    4) Electrical resistivity should be less than 0.01724 Ω mm2/m @ 20 oC in annealed condition.
    5) Supplier should forward test certificate for insulation paper, copper conductor and enamel before manufacturing for MTM approval.
    6) No. of transposition shall be provided in supplier Data Sheet.
    7) Dimensional detail of CTC shall be submitted to MTM for review and approval.
    8) Paper covering shall be closely packed without gaps. CTC shall be free from twist & other form of distortion. Paper covering shall be tight and free from
    crack, puncture and inclusion of foreign matters, creases and other defects. Loose covering is NOT ACCEPTABLE.
    9) Drum size: Flange (max) 1600 mm, Outer width (max) 1000 mm, Bore (min) 120 mm, weight per drum + copper (max) 5000 kg
    10) Lubricant used for CTC transposition process shall be with an inhibitent insulating oil according to IEC 60296 with improved stability againts oxidation.

    Requirement per Job= 4,188 kg
    Total job required:
    PMU Pasir Besar = 2 Job

    7.BUNCH CONDUCTOR, 45-305, QTY:12324

    NOTE FOR BUNCH CONDUCTOR:- 5988
    1) Type of papers and test requirements: 6162
    As per MS-16, Specification For Paper Covered Rectangular Copper Conductor, Rev.2)
    2) Inner layer: (Insulation paper from Weidmann and Munskjo only)
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1.
    Inner layer shall be applied in butt lap without gap in the butt. Each layer shall be staggered with respect to the undernearth layer by 33% of paper width (approx).
    3) Outermost layer: (Insulation paper from Weidmann and Munskjo only)
    Thermally Upgraded Paper as per IEC 60554-3-5, grade 5A4-1M1
    Outermost 2 layers shall be interlock by 50%.
    4) Supplier should confirm width of paper before manufacturing.
    5) Supplier should forward test certificate for insulation paper and copper conductor before manufacturing for MTM approval.
    6) Drum size: Flange (max) 1016 mm, Outer width (max) 300 mm, Bore (min) 70 mm, weight per drum + copper (max) 500 kg

    Requirement per Job= 6,162 kg
    Total job required:
    PMU Pasir Besar = 2 Job

    8.RECTANGULAR COPPER WIRE (PICC), 45-305, QTY:2144

    NOTE FOR BUNCH CONDUCTOR:-
    1) Type of papers and test requirements:
    As per MS-16, Specification For Paper Covered Rectangular Copper Conductor, Rev.2)
    2) Inner layer: (Insulation paper from Weidmann and Munskjo only)
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1.
    Inner layer shall be applied in butt lap without gap in the butt. Each layer shall be staggered with respect to the undernearth layer by 33% of paper width (approx).
    3) Outermost layer: (Insulation paper from Weidmann and Munskjo only)
    Thermally Upgraded Paper as per IEC 60554-3-5, grade 5A4-1M1
    Outermost 2 layers shall be interlock by 50%.
    4) Supplier should confirm width of paper before manufacturing.
    5) Supplier should forward test certificate for insulation paper and copper conductor before manufacturing for MTM approval.
    6) Drum size: Flange (max) 1016 mm, Outer width (max) 300 mm, Bore (min) 70 mm, weight per drum + copper (max) 500 kg

    Requirement per Job= 1,072 kg
    Total job required:
    PMU Pasir Besar = 2 Job

    9.Contra Shield 45-305, QTY:40

    NOTE FOR PICC:-
    1) Rp 0.2% Proof Stress: Min. 190 MPa
    2) SUPPLIER TO FORWARD TECHNICAL DATA SHEET (TDS) FOR MTM APPROVAL BEFORE PRODUCTION.
    3) Type of papers and test requirements:
    As per MS-16, Specification For Paper Covered Rectangular Copper Conductor, Rev.2)
    4) Inner layer: (Insulation paper manufacturer from 1) Weidmann, (Switzerland/ China). 2) Munskjo, Sweden. 3) Pucaro, Germany)
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1. Inner layer shall be applied in butt lap without gap in the butt.
    Each layer shall be staggered with respect to the underneath layer by 33% of paper width (approx.).
    5) Outermost layer: (Insulation paper manufacturer from 1) Weidmann, (Switzerland/ China). 2) Munskjo, Sweden. 3) Pucaro, Germany)
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1. Outermost 2 layers shall be interlock by 50%.
    6) Supplier to confirm width of paper before manufacturing.
    7) Supplier to forward test certificate for insulation paper and copper conductor before manufacturing for MTM approval.
    8) Drum size: Flange (max) 1016 mm, Outer width (max) 300 mm, Bore (min) 70 mm, weight per drum + copper (max) 500 kg

    Requirement per Job= 20 kg
    Total job required:
    PMU Pasir Besar = 2 Job

    10.COPPER CONDUCTOR, 90-310, QTY:2914

    Requirement per Job= 1,457 kg
    Total job required:
    PMU OZANA = 2 Job

    11.LV Winding, QTY:14892

    Requirement per Job= 7,446kg
    Total job required:
    PMU OZANA = 2 Job

    NOTE FOR CTC:-
    1) Type of papers and test requirements:
    1.1) As per MS-43, Specification for Continuously Transposed Conductor (CTC), Rev. 1
    1.2) Paper covering shall be applied on CTC by helical lapping of paper tapes with all layers in same direction. Paper lapping shall be tight and
    continuous in each layer. No adhesive or bonding material shall be used except for anchoring paper end.
    2) Inner layer: (Insulation paper from Weidmann, Munskjo and Pucaro only)
    2.1) Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1.
    2.2) Inner layers (Kraft paper) shall be applied in butt-laps without any gap in the butt. Each layer shall be staggered (progressively displaced) with
    respect to the underneath layer, by 33% of paper width.
    3) Outermost layer: (Insulation paper from Weidmann, Munskjo and Pucaro only)
    3.1) Thermally Upgraded Insulated paper as per IEC 60554-3-5, grade 5A4-1M1
    3.2) Outermost two layers shall be interlocked by 50% paper width
    4) Electrical resistivity should be less than 0.01724 Ω mm2/m @ 20 oC in annealed condition.
    5) Supplier should forward test certificate for insulation paper, copper conductor and enamel before manufacturing for MTM approval
    6) No. of transposition shall be provided in supplier Data Sheet.
    7) Dimensional detail of CTC shall be submitted to MTM for review and approval.
    8) Paper covering shall be closely packed without gaps. CTC shall be free from twist & other form of distortion. Paper covering shall be tight and free from crack, puncture and inclusion of foreign matters, creases and other defects. Loose covering is NOT ACCEPTABLE.
    9)Drum size: Flange (max) 1600 mm, Outer width (max) 1000 mm, Bore (min) 120 mm, weight per drum + copper (max) 5000 kg
    10)Lubricant used for CTC transposition process shall be with an inhibitent insulating oil according to IEC 60296 with improved stability against oxidation.

    12.BUNCH CONDUCTOR, 90-310, QTY:22302

    NOTE FOR BUNCH CONDUCTOR:-
    1) Type of papers and test requirements:
    As per MS-16, Specification For Paper Covered Rectangular Copper Conductor, Rev.2)
    2) Inner layer: (Insulation paper from Weidmann and Munskjo only)
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1.
    Inner layer shall be applied in butt lap without gap in the butt. Each layer shall be staggered with respect to the undernearth layer by 33% of paper width (approx).
    3) Outermost layer: (Insulation paper from Weidmann and Munskjo only)
    Thermally Upgraded Paper as per IEC 60554-3-5, grade 5A4-1M1
    Outermost 2 layers shall be interlock by 50%.
    4) Supplier should confirm width of paper before manufacturing.
    5) Supplier should forward test certificate for insulation paper and copper conductor before manufacturing for MTM approval.
    6) Drum size: Flange (max) 1016 mm, Outer width (max) 300 mm, Bore (min) 70 mm, weight per drum + copper (max) 500 kg
    Requirement per Job= 11,151kg
    Total job required:
    PMU OZANA = 2 Job

    13.REGULATING WINDING, QTY:3200

    Requirement per Job= 1,600kg
    Total job required:
    PMU OZANA = 2 Job

    NOTE FOR BUNCH CONDUCTOR:-
    1) Type of papers and test requirements:
    As per MS-16, Specification For Paper Covered Rectangular Copper Conductor, Rev.2)
    2) Inner layer: (Insulation paper from Weidmann and Munskjo only)
    Thermally upgraded insulating paper as per IEC 60554-3-5, grade 5A4-1M1.
    Inner layer shall be applied in butt lap without gap in the butt. Each layer shall be staggered with respect to the undernearth layer by 33% of paper width (approx).
    3) Outermost layer: (Insulation paper from Weidmann and Munskjo only)
    Thermally Upgraded Paper as per IEC 60554-3-5, grade 5A4-1M1
    Outermost 2 layers shall be interlock by 50%.
    4) Supplier should confirm width of paper before manufacturing.
    5) Supplier should forward test certificate for insulation paper and copper conductor before manufacturing for MTM approval.
    6) Drum size: Flange (max) 1016 mm, Outer width (max) 300 mm, Bore (min) 70 mm, weight per drum + copper (max) 500 kg

    14.RECTANGULAR COPPER WIRE, QTY:210

    Requirement per Job= 105kg
    Total job required:
    PMU OZANA = 2 Job

    15.COPPER CONDUCTOR, 30-306, QTY:1756

    Requirement per Job= 878kg
    Total job required:
    PMU Gurun Rehab = 2 Job

    16.LV WINDING 30-306, QTY:7728

    Requirement per Job= 3,864kg
    Total job required:
    PMU Gurun Rehab = 2 Job

    17.BUNCH CONDUCTOR 30-306, QTY:12672

    Requirement per Job= 6,336kg
    Total job required:
    PMU Gurun Rehab = 2 Job

    18.REGULATING 30-306, QTY:1984

    Requirement per Job= 992KG
    Total job required:
    PMU Gurun Rehab = 2 Job

    19.CONTRA SHIELD 30-306, QTY:50

    Requirement per Job= 25KG
    Total job required:
    PMU Gurun Rehab = 2 Job